Abstract
In this study, polyethylene and zeolite, as media in two-stage biological aerated filters (BAF), were evaluated for simultaneous removal of ammonia nitrogen and organics in micro-polluted water under low temperature conditions. For specific source water, the contaminants removal characteristics are evaluated by single-factor experiment to determine the suitable pH, air-water ratio (AWR) and hydraulic load ratio (HLR). Ammonia nitrogen and permanganate index in BAFs were promoted effectively with pH = 7~8, AWR = 1.0:1.0~2.0:1.0, HLR = 1~4 m3/(m2·h), low pollution loads and a temperature of 10°C. Based on the response surface analysis, the optimum parameters were as follows: pH of 7.94, AWR of 1.41:1.0 and HLR of 1.39 m3/(m2·h), for simultaneous removal of ammonia nitrogen and permanganate index, their removal rates were respectively 59.76% and 18.16%. BAF has a great advantage in emergency treatment of low temperature micro-polluted water, and response surface analysis can be used to optimize operating parameters.
Funder
national science and technology major project for water pollution control and treatment
Publisher
Korean Society of Environmental Engineering
Subject
Environmental Engineering
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献