Affiliation:
1. Instituto de Investigaciones Eléctricas, México
Abstract
This article presents a new approach of partial discharges (PD) source location in power cables. The main advantage of this approach is the detection of the propagation direction of the PD. The method provides a pattern named by the authors PD+D, which, in contrast to the well–known phase-resolved partial discharge (PRPD) pattern, graphically shows the direction of PD propagation and uses the polarity of a sensor array on top of the magnitudes of the positive and negative parts of each PD pulse to detect the direction of propagation, is described in detail. The proposed technique is useful for the evaluation and diagnosis of power cables, since it can identify incipient faults. The attained results that demonstrate the value of this methodology and their scope and limitations are discussed.