Static balance duct design method and temperature dependent variable air volume systems

Author:

Kong Kok Haw1ORCID,Chong Wen Tong1

Affiliation:

1. Faculty of Engineering, Department of Mechanical Engineering, University of Malaya, Kuala Lumpur, Malaysia

Abstract

In hot and humid tropical countries, the air-conditioning system has a high energy usage in commercial buildings. This study introduces a static balance duct design method for a temperature dependent variable air volume system. Ducts are looped together, which cause the air to self-balance and minimize the pressure loss across the duct network. The static balance duct network can easily identify the critical zone of highest pressure loss. This zone appears at the longest duct length from the air source and is always consistent for different load conditions. The air supplied to this critical zone is controlled by the zone temperature sensor, which directs feedback to the variable frequency drive fan of the air-handling unit. The rest of the variable air volume terminal units are zone temperature controlled. The duct looping design mitigates the problems in pressure variations and complements the temperature dependent control strategy. An open office case study is carried out to demonstrate the merit of the static balance duct design method. An actual installation was completed in a shopping mall. The recorded temperature readings verified that the static balance duct network and temperature dependent variable air volume air-conditioning system is operational and functional. Approximately 27% energy savings is achieved compared to the constant air volume system. Practical application: The static balance duct design method is a combination of equal friction duct design method and a loop duct network. This static balance duct network can identify the critical zone of highest pressure loss and this zone is always consistent. In this temperature-dependent variable air volume (TDVAV), the variable air volume (VAV) terminal unit at the critical zone is eliminated. The zone temperature sensor at the critical zone provides direct feedback to the variable frequency drive fan. All other terminal units are temperature dependent. The static balance TDVAV system enhances energy savings, improves the performance of VAV system and reduces the faults for VAV systems.

Publisher

SAGE Publications

Subject

Building and Construction

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3