Affiliation:
1. National Institute of Occupational Health, Lersoe Parkalle 105, DK-2100 Copenhagen, Denmark
Abstract
A multipoint (8 channel) single tracer-gas measuring unit is described. Using a gas chromatograph for the tracer (SF6) analysis a 9 s sampling interval was achieved. The detection limit was 0.03 ppb. The workshop (9700 m 3) was ventilated using the displacement design principle. The air supply rate by mechanical ventilation was 7.7 m3s-1 and infiltration was added to this at a rate of 6.3 m3 s-1. The displacement air flow created two different flow regions in the workshop. Heat and air pollutants accumulated in an upper region giving acceptable working conditions in the lower region (the zone of occupancy). Consequently, displacement ventilation has potential for improving air quality in high-ceiling workshops with a heat load.
Subject
Building and Construction
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献