Affiliation:
1. Gershman, Brickner and Bratton, Inc., 2735 Hartland Road, Falls Church, VA 22043, U.S.A.
Abstract
Polychlorinated dibenzo-p-dioxins (PCDD) and polychlorinated dibenzofurans (PCDF) may enter an incinerator with the waste, be created in poor combustion or form in post-combustion zones under certain conditions of temperature and oxygen. Tests of MSW burning plants show a wide range of emissions of PCDD and PCDF. Diagnostic tests show the relationship between combustion conditions and the emission of PCDD/DF before and after emission controls. Mixing effectiveness, tightness of control, moisture, furnace and post-furnace temperatures, and the use of lime and reduced temperatures for acid-gas control all have an effect on emissions of trace organics. Carbon monoxide (CO), oxygen, moisture and furnace temperature have been found to be closely related to PCDD/PCDF emissions. By control of temperature and/or oxygen, and the use of CO as an indicator, it is possible to find and maintain optimum combustion conditions so as to minimize dioxins and furans. Plants having acid-gas controls reduce emissions below those achieved by good combustion alone.
Subject
Pollution,Environmental Engineering
Cited by
46 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献