A numerical study on effect of intra and inter spaced winding configuration on performance of oil forced transformer cooling system

Author:

Muralikrishna Yamala1,Satyanarayana Reddy Seerapu Siva1,Sahu Mithilesh Kumar2ORCID,Mohan Jagadeesh Kumar M1

Affiliation:

1. Department of Mechanical Engineering, GVP College of Engineering (A), Visakhapatnam, India

2. Department of Mechanical Engineering, OP Jindal University, Raigarh, India

Abstract

The present work aims at investigating, numerically, the heat transfer characteristics of transformer cooling system under forced circulation for three different winding configurations. The purpose of a transformer cooling system is to keep the hot spot temperature within the critical value for a long life of transformer, which increases with enhanced cooling of transformer windings. Thus, two different winding configurations are modeled by providing space within the windings (an intra-space model) and in between the windings (an inter-space model) to improve the fluid-solid interaction. A conventional winding, without spacing, is also modeled for comparative study. A 315 kVA, 3-phase core type transformer is taken as the base model from which the winding and core specifications are obtained analytically. Parameters chosen to measure the influence of winding configuration are local temperature distribution in the windings and core and maximum transformer temperature. Results are obtained for all three models with varying space for various cooling mediums like naphthenic oil, silicon oil, and synthetic ester oil at flow velocities ranging from 0.72 m/s to 2.16 m/s. It is observed that the gap between the windings, interspacing, decreases the secondary winding temperatures, while it increases the core and primary winding temperatures. However, the intra spacing configuration finds a drop in local temperatures at all locations of the transformer windings and core. The enhanced heat dissipation to the cooling agent, with intra spacing winding configuration, reduces the maximum transformer temperature. Contrasting to the above, the inter-space model has an adverse effect on maximum temperature at all widths of space considered. Quantitatively, the space within the transformer reduces the maximum temperature by 5% in comparison with the space between the windings. The increased velocity of the cooling medium, Naphthenic oil, from 0.72 m/s to 2.16 m/s reduces the maximum temperature by 4.5 units. The study made to know the role of cooling medium discloses that the synthetic ester oil shows better performance for reducing temperature values due to its highly viscous nature.

Publisher

SAGE Publications

Subject

Mechanical Engineering,Energy Engineering and Power Technology

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3