Affiliation:
1. Department of Mechanical Engineering, Faculty of Engineering, Kharazmi University, Tehran, Iran
Abstract
In this study, the transient performance of a qanat source heat pump is investigated using a TRNSYS-MATLAB co-simulator. The water/ethylene glycol-to-air compression heat pump and the helical coil heat exchanger, which is used to inject heat to or to extract heat from the qanat water, are mathematically modeled in matrix laboratory (MATLAB), and then, coupled to transient systems simulation (TRNSYS) model to evaluate the system transient performance and calculate the heating and cooling loads of the case study building. Comparison of the performance of the qanat source heat pump with an air source heat pump showed that the coefficient of performance of the qanat source heat pump is at least 5% and at most 34% higher than that of the air source heat pump. By increasing the flow rate of the working fluid in the helical coil heat exchanger from 2 L/min to 8 L/min, the coefficient of performance of the qanat source heat pump increases at least 12% and at most 34.1%. The maximum increase in energy efficiency ratio and free energy ratio of the system by the similar increase in the flow rate is 46.4% and 24.8%, respectively. The exergy analysis of the qanat source heat pump reveals that the minimum and maximum exergy efficiency of the system is 32% and 85.5%, respectively. The findings also indicate that the most exergy destruction occurs in the condenser in heating mode and in the evaporator in cooling mode.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Environmental Engineering
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献