Local Discomfort Caused by Draft Perception in a Space Served by Displacement Ventilation System in the Tropics

Author:

Yu W. J.1,Cheong K. W. D.2,Sekhar S. C.2,Tham K. W.2,Kosonen R.3

Affiliation:

1. Department of Building, National University of Singapore, Singapore 117566,

2. Department of Building, National University of Singapore, Singapore 117566

3. Halton Oy, Haltonintie 1-3, Kausala 47400, Finland

Abstract

This paper reports a subjective study in a field environmental chamber (FEC) served by a displacement ventilation (DV) system. Sixty tropically acclimatised subjects, 30 males and 30 females, were engaged in sedentary office work for 3h. The subjects were exposed to three vertical air temperature gradients (nominally 1, 3 and 5K·m 1) between 0.1 and 1.1m heights and three room air temperatures (20, 23 and 26°C) at 0.6m height. The object of this work was to investigate effects of temperature gradient and room air temperature on local discomfort due to air movement at different thermal sensations. The results indicated that vertical temperature gradient had an insignificant impact on draft perception. Draft perceptions at foot, calf, thigh and arm were affected by both overall and local thermal sensations. A cold sensation would increase the risk of draft complaints and a warm sensation would increase the percentage dissatisfied due to insufficient air movement.

Publisher

SAGE Publications

Subject

Public Health, Environmental and Occupational Health

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3