Abstract
The climate of Yangtze River Basin in China is cold and humid in winter. Conventional air-conditioning systems may cause high energy consumption and uncomfortable microclimatic conditions especially for lower body of indoor occupants. This study investigated four personalized seat heating systems, in a typical office room in Shanghai during winter, based on heated floor panels including heated floor panels + ordinary chair (HF-OC), heated floor panels + insulated chair (HF-IC), heated floor panels +insulated chair and leg box (HF-IC-LB) and overall personalized heating (OPH). The surface temperature of walls and heated floor panels, and the indoor air temperature at different positions were recorded with thermocouples. The hourly energy consumptions of the proposed personalized seat heating systems were measured and compared with a conventional split type air conditioner. Questionnaires of thermal sensation and comfort were carried out among 10 university students. Compared with HF-OC, HF-IC could improve the thermal comfort to a certain extent, while HF-IC-LB provided the optimal thermal micro-environment for the lower body other than other body parts. The OPH systems were proven effective to provide satisfactory thermal environment for all body parts at lower indoor temperature (12–16°C) with much less energy consumption than room air conditioners.