Affiliation:
1. Anhui Province Key Laboratory of Electric Fire and Safety Protection (State Grid Laboratory of Fire Protection for Transmission and Distribution Facilities), State Grid Anhui Electric Power Research Institute, Hefei, China
2. School of Safety Science and Emergency Management, Wuhan University of Technology, Wuhan, China
Abstract
In this study, aqueous film-forming foam, fluoroprotein foam, and synthetic foam were applied to extinguish the transformer oil pool fires. The fire-extinguishing performance and burn-back resistance were investigated using a laboratory fire-extinguishing system. Moreover, the emission products were analyzed to evaluate the gas-phase pollution characteristics. Results show that aqueous film-forming foam presents the highest fire-extinguishing efficiency, while fluoroprotein foam has the best burn-back performance. Flue gas and gas chromatography–mass spectrometer analyses demonstrate that the use of fluoroprotein foam results in much higher CO emissions than other foams, and the pollutants are mainly from various hydrocarbons produced by incomplete combustion of transformer oil. Synthetic foam and aqueous film-forming foam lead to higher SO2 and NO emissions, and pollutants are mainly dominated by alcohols and ethers. Noteworthily, when using aqueous film-forming foam to extinguish oil pool fire, a persistent organic pollutant, perfluorooctanoic acid, is detected in the gas phase.
Funder
Science and Technology Project of State Grid Corporation of China
Subject
Mechanical Engineering,Mechanics of Materials,Safety, Risk, Reliability and Quality
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献