Affiliation:
1. College of Aerospace and Civil Engineering, Harbin Engineering University, Harbin, China
Abstract
The Halon 1301 fixed gas fire extinguishing system used in ship engine rooms has been banned from production all over the world, because halon destroys the ozone layer. Therefore, it is necessary to find an environmentally friendly, compatible and efficient alternative firefighting system. In this study, we performed fire extinguishing tests in an ISO9705 standard room for four alternative fire extinguishing agents, as well as Halon 1301. The fire extinguishing efficiency of each agent was determined based on its cooling effect, dilution effect of oxygen concentration, the extinguishing time of the oil pool fire and the re-ignition probability of the wood stack. The test results provide data support for the selection of alternatives of Halon 1301 from the aspect of fire extinguishing efficiency. Among these results, Novec 1230 had the best ability to put out the oil pool fire, and HFC-227ea suppressed the wood stack fire the best. The difference between the cooling ability of each fire extinguishing agent was small, and the inert gas (IG-541) displayed the best ability to dilute oxygen. Hot aerosol required the longest time to extinguish fire. Consequently, under the existing design standards, HFC-227ea had the better firefighting efficiency, more suitable to replace Halon 1301.
Funder
national key research and development program of china
Subject
Mechanical Engineering,Mechanics of Materials,Safety, Risk, Reliability and Quality
Cited by
13 articles.
订阅此论文施引文献