Affiliation:
1. State Key Laboratory of Fire Science University of Science & Technology of China Hefei, Anhui, 230026, China
2. Division of Building Science and Technology City University of Hong Kong Hong Kong, China
Abstract
Series fire tests simulating cable fires in plenum caused by exposed and aged combustible cables were carried out in a real-scale flatletmodel containing burn room, ceiling plenum, and target room. A special communication cable type insulated with HDPE and sheathed with LLDPE was utilized. A related fire reference scenario was designed to simulate how cables in plenum were involved in a fire from potential fire loads to substantial fuel by the role of an external flaming source and to characterize related fire issues. Major concerns are that how various amounts, various ignition means and different ventilation rates impact on fire performances (heat release rate, smoke temperature, smoke obscuration, combustion products, and toxicity) of cables in plenum. It is found that influences of these parameters are obvious. The burning of exposed tested cables in plenum easily poses a high potential of fire hazard even at a relatively low fire load.
Subject
Mechanical Engineering,Mechanics of Materials,Safety, Risk, Reliability and Quality
Reference11 articles.
1. 1. Holt, Mike (2001). Technology-wiring Definitions: Part 2, Electrical Construction and Maintenance [H.W. Wilson–AST] , CEE News, 100(3): 74–75 .
2. Toxic Hazard evaluation of plenum cables
3. Fire initiation and spread in overloaded communication system cable trays
4. 11. Daly, J.M. (1991). Cable Testing for Flame Propagation and Toxicity , Wire Journal International, 24(9): 221–227 .
5. Comparison of large-and small-scale heat release tests with electrical cables
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献