Hardware in the Loop-Based Testing of Three Schemes for Mitigation the Effect of Unsymmetrical Grid Faults on DFIG
Author:
Ebrahim Essamudin Ali1, Nashed Maged N. F.1, Eskander Mona N.1
Affiliation:
1. Power Electronics and Energy Conversion Department, Electronics Research Institute, Joseph Tito St., Huckstep, Qism El-Nozha, Cairo Governorate, Cairo, EGYPT
Abstract
This paper presents three-proposed schemes to mitigate the effect of unsymmetrical voltage sag fault on a wind-driven grid-connected Double Fed Induction Generator (DFIG). The first tested scheme comprises a static compensator (STATCOM) connected to the DFIG stator, while a three-phase parallel RL external impedance is connected to the rotor circuit in the second scheme. The STATCOM and the added rotor impedance are connected simultaneously in the third scheme. The effect of applying the three schemes on the responses of the stator and rotor voltages and currents, the dc-link voltage and current, the electrical torque, and the rotor speed during an unsymmetrical voltage sag are presented and compared at sub-and super-synchronous speeds. All systems were emulated, implemented, and tested through an OPAL RT-4510 Digital Real-Time Simulator (DRTS) in a Hardware-In-the-Loop (HIL) application. The internal Field-Programmable Gate Array (FPGA) chip assisted in using this platform as a Rapid Control Prototyping (RCP) for virtual mitigation control and testing. The Matlab/ Simulink RT-lab software packages combination helped in the RT development environment. All real-time waveforms of parameters for the proposed scenarios were monitored through the HIL-controller and data acquisition interface and then compared with the simulated results. The results reveal that the simulation waveforms and the real time waveforms are congruent. Results prove the better performance of the DFIG during unsymmetrical voltage sag for sub-synchronous speed when applying both protection schemes, while best results are obtained when using only the rotor impedance at super-synchronous speed operation of the DFIG.
Publisher
World Scientific and Engineering Academy and Society (WSEAS)
Subject
Electrical and Electronic Engineering,Energy (miscellaneous)
Reference31 articles.
1. M. Eskander, M. Saleh, M. El-Hagry, “Performance of Double Fed Induction Machine at Sub- and Super- Synchronous Speed in Wind Energy Conversion System”, Journal of Power Electronics, JPE 9-4-7, 2009, pp. 575-58. 2. Yun Wang, Qiuwei Wu, Honghua Xu, Qinglai Guo, and Hongbin Sun., “Fast Coordinated Control of DFIG Wind Turbine Generators for Low and High Voltage Ride-Through”, Energies 2014, 7, 4140-4156. 3. M. N. Eskander, M.A.Saleh, Maged N.F.Nashed, S. Amer., “Superiority of LVRT of Grid Connected Wind Energy Conversion System Using Unified Power Quality Controller”, International Electrical Engineering Journal, Vol. 6, no.6, 2015, pp. 1925-1930. 4. G. Parameswari and H. Sait, “A comprehensive review of fault ride-through capability of wind turbines with a gridconnected doubly fed induction generator”, Int. Trans. Elec. Energy Syst., Vol. 30, no. 8, 2020, pp. 1–30, https://doi.org/10.1002/2050- 7038.12395. 5. A. Rola´n, F. Co´rcoles, J. Pedra, “Behavior of the doubly-fed induction generator exposed to unsymmetrical voltage sags", IET Electrical Power Applications, Vol. 6, no. 8, 2012, pp. 561–574.
|
|