Author:
Abdelaziz A.Y.,Ibrahim Amr M.,Salem Reham H.
Abstract
This paper presents optimal phasor measurement units (PMUs) placement algorithms for power system observability. The optimal placement problem (OPP) is formulated such that minimizing the number of PMU installations for full networkobservability. Three approaches, in this paper, are introduced aiming at reducing the computational burden in Optimal Placement problems. Depth First Search, Simulated Annealing and Minimum Spanning Tree as well as their differences and relations are discussed in details. The OPP methodologies applied include the system observablility during normal operating conditions, as well as during single branch forced outages. In order to improve the speed of convergence, an initial PMU placement is provided by graph-theoretic procedure. The IEEE 14-bus, 118-bus standard test power systems and New England 39-bus test systems are used for simulation purposes.Keywords: Phasor Measurement Unit (PMU); Observability; Depth First Search; Simulated Annealing Method; Minimum Spanning Tree; Optimal PMU Placement (OPP)
Publisher
African Journals Online (AJOL)
Cited by
16 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
1. Implementation of a Wide Area Monitoring System for the Power Transmission Grid of Bangladesh;2023 International Conference on Information and Communication Technology for Sustainable Development (ICICT4SD);2023-09-21
2. A System-Based Framework for Optimal Sensor Placement in Smart Grids;2023 IEEE Belgrade PowerTech;2023-06-25
3. Efficiency of post-processing in PMU based state estimation of renewable energy microgrids;2023 IEEE Belgrade PowerTech;2023-06-25
4. An Analysis of Effective and Efficient Integration of Distributed Power Generation;2022 International Conference on Futuristic Technologies (INCOFT);2022-11-25
5. Optimizing Power System Observability Using GAMS;2022 IEEE PES 14th Asia-Pacific Power and Energy Engineering Conference (APPEEC);2022-11-20