This paper investigated the tripping profile of the 33 kV feeder of Ugbowo 2 x 15 MVA, 33/11 kV electric powerdistribution network. The annual data of daily tripping of the 33 kV feeder from September 2019 to August 2020were collated and collected from the Ugbowo injection substation. The daily outage of the 33 kV feeder was usedto compute the monthly and yearly tripping profile of the sub-transmission line (33 kV feeder) of the Ugbowoinjection substation. The monthly and yearly failure rate, MTTR, MTTF, MTBF, availability, unavailability, SAIFI,SAIDI, ASAI, ASUI, etc. for the period of twelve (12) months were analyzed using the Load Point Indices (LPI)and Microsoft Excel was used graphically to interpret the results of the tripping profile of the 33 kV feeder. Theresults obtained from the analyses of the 33 kV feeder of the network showed that yearly failure rate, MTTR,MTTF, MTBF, unavailability, availability, SAIFI, SAIDI, ASAI and ASUI were 4.32%, 6.520 h, 23.148 h, 29.668h, 21.98%, 78.02%, 0.0358 interruptions/customer/yr, 0.2336 h/customer/yr, 78.03%, and 21.97%, respectively.These results revealed that the performance indices of the 33 kV feeder with annual total outage frequency (SAIFI)and percentage availability (ASAI) were a far cry from the recommended values of the internationally acceptablestandard value (IASV) of 0.01 and 99.99% respectively. This poses a threat to the reliability and availability ofelectricity supply to consumers.
Publisher
African Journals Online (AJOL)
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
1. Challenges in Evaluating Quality of Service in Modern Power Grids;2023 IEEE 15th International Conference on Computational Intelligence and Communication Networks (CICN);2023-12-22
2. Quality of Supply and Customer Engagement in the Energy Industry;Fostering Cross-Industry Sustainability With Intelligent Technologies;2023-09-29