EXPERIMENTAL AND CFD INVESTIGATION OF R410A DISTRIBUTORS FOR AIR CONDITIONER

Author:

HAN QING1,ZHANG CHI1,CHEN JIANGPING1

Affiliation:

1. Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, No. 800 DongChuan Road, Shanghai 200240, P. R. China

Abstract

In order to obtain a higher heat transfer coefficient of refrigerant flow, the diameter of tubes tends to be smaller and smaller, which leads to large pressure drop of the refrigerant flow. Therefore, multiple numbers of parallel refrigerant passages are employed by using distributors. It is very important to distribute the two-phase refrigerant evenly into each tube, otherwise the thermal performance is significantly deteriorated. The performance reduction by flow mal-distribution could be as large as 20–25%. The goal of this paper is to investigate the influence of different configurations to the performance of refrigerant distributors by experiments and computational fluid dynamic code. The effects of mass flow rate and quality of distributor inlet on the characteristics were also quantitatively considered. In this study, an experiment test rig was built to measure the mass flow rate and quality of four circuits after using distributors under different conditions respectively. Refrigerant R410A was used as working fluids. Three classic types (jet, cyclone and reservoir) of distributors with four paths were manufactured and tested under relevant operating conditions. The inlet temperature was 4°C, mass flow rate range was 50–100 kg/h and the quality range was 0.1–0.3. Experimental results show that the maximum deviation of mass flow rate for jet, cyclone and reservoir type is 13.0%, 21.6% and 10.9%, respectively; the maximum deviation of quality was 0.08, 0.10 and 0.05, respectively. In addition, the standard deviation of mass flow rate and quality over four paths were selected to evaluate the performance of different type distributors. The results show that the performance of jet and reservoir are better than cyclone. The flow behavior of two-phase refrigerant such as phase distribution and separation phenomena was studied by Computational Fluid Dynamics (CFD). The flow pattern of inlet for R410A was investigated and used in the present model. The results in the present model show good and reasonable approximation with experimental data which validate the CFD simulation. CFD simulation analysis elucidates the mechanics which shows how the configuration and operation conditions affect the refrigerant distribution.

Publisher

Springer Science and Business Media LLC

Subject

Fluid Flow and Transfer Processes,Renewable Energy, Sustainability and the Environment,Control and Systems Engineering

Cited by 13 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3