Validation of MICA Legionella for Enumeration of Legionella pneumophila in Sanitary Waters and Cooling Tower Waters: AOAC Performance Tested MethodSM 032201

Author:

Passot Fanny1ORCID,Peslier Sabine1ORCID,Benzinger M Joseph2ORCID,Blackburn Jonathan2ORCID,Thompson Wesley2ORCID,Bastin Benjamin2ORCID,Dumont Audrey1ORCID,Dukan Sam1ORCID

Affiliation:

1. DIAMIDEX, Grand Luminy Technopole, Zone Luminy Entreprise Biotech , Case 922, 163 Avenue de Luminy , 13288 Marseille Cedex 09, France

2. Q Laboratories , Cincinnati, OH 45204, USA

Abstract

Abstract Background Frequent testing for Legionella concentration in water is required by most health risk monitoring organizations worldwide. Domestic hot water and cooling tower water networks must be regularly controlled to prevent Legionnaires’ disease, a potentially deadly lung infection. MICA Legionella is the fastest culture-based detection method for all serogroups of Legionella pneumophila, with automatic enumeration in 48 h and no need for confirmation. Objective This study compares the performance and robustness of MICA Legionella with the reference method ISO 11731:2017 for the enumeration of culturable L. pneumophila. Methods MICA Legionella and ISO 11731:2017 results were compared for domestic hot water and cooling tower water. Inclusivity and exclusivity were tested on reference and environmental strains. Ruggedness, lot-to-lot consistency, and stability of the reagents kit were also studied. Results Enumeration of L. pneumophila by MICA Legionella was statistically equivalent to ISO 11731:2017 in both matrixes. In cooling tower waters, MICA Legionella showed better sensitivity than ISO 11731:2017. It presented a 94% sensitivity and a 97% specificity. Conclusion MICA Legionella is a highly sensitive and specific method for culturable L. pneumophila enumeration. It presents, in 48 hours, equivalent or better results than ISO 11731:2017. Its protocol is robust to variations. Its reagents kit is stable for up to 18 months. Highlights MICA Legionella is a robust and reliable method for the enumeration of culturable L. pneumophila in domestic and cooling tower water. It reduces significantly the number of sample pretreatments required in ISO 11731:2017. Automatic identification and enumeration of L. pneumophila microcolonies eliminates the requirement to have skilled analysts and limits the results variability. It also greatly reduces the time to results to 48 h instead of 7–10 days with ISO 11731:2017 while providing statistically equivalent results.

Funder

Diamidex

Publisher

Oxford University Press (OUP)

Subject

Pharmacology,Agronomy and Crop Science,Environmental Chemistry,Food Science,Analytical Chemistry

Cited by 2 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3