Performance investigation of a micro-channel flat separated loop heat pipe system for data centre cooling

Author:

Hu Menglong1,Luo Liang1,Badiei Ali2,Chen Fucheng1,Zheng Siming1,Wang Zhangyuan12,Zhao Xudong2

Affiliation:

1. School of Civil and Transportation Engineering, Guangdong University of Technology, 100 Waihuan Xi Road, Higher Education Mega Centre, Guangzhou 510006, Guangdong Province, P.R. China

2. Centre for Sustainable Energy Technologies, University Hull, Cottingham Road, Hull, HU6 7RX, UK

Abstract

Abstract This paper investigates a novel micro-channel flat separated loop heat pipe system for cooling the information technology equipment in the data centres through theoretical and experimental analysis and by assessing the impact of the inlet water temperature on system performance. A computer model is developed to simulate the steady-state performance of the micro-channel flat separated loop heat pipe system. After comparing the experimental and modelling results, the new and conventional system under the same working conditions, the model is validated yielding high accuracy in predicting the performance of the micro-channel flat separated loop heat pipe system with recorded error being limited to 2.16–8.97%. The new system has better performance than the conventional system. Under the operating conditions of heat load intensity of 1,000 W/m2, water flow rate of 0.28 m3/h, refrigerant filling rate of 30%, ambient air temperature of 26°C, and evaporator and condenser height difference of 0.8 m, the performance of the system has been explored at inlet temperature from 15 to 24°C with increments of 3°C. The system’s averaged heat transfer efficiency was found to decrease with the increase in inlet temperature. This research provides valuable insight into the data centre information technology equipment cooling, which is of great significance for energy saving and environmentally friendly operation of data centres.

Publisher

Oxford University Press (OUP)

Subject

General Environmental Science,Architecture,Civil and Structural Engineering

Reference33 articles.

1. Comparison of sustainable information technologies for companies;Onur;Int J Low-Carbon Tech,2015

2. The European code of conduct on data centre energy efficiency;Renewable Energy Unit;Version 3.0. European Commission,2015

3. Energy, performance and cost efficient datacenters: A survey;Zakarya;Renew Sust Energ Rev,2018

4. Simulation on vertical microchannel evaporator for rack-backdoor cooling of data center;Zhan;Appl Therm Eng,2020

5. A review of air conditioning energy performance in data centers;Ni;Renew Sust Energ Rev,2017