Author:
Valchev Slav,Mihaylov Ivan
Abstract
Object of the present study is an experimental determination of energy efficiency parameters of air handling unit with integrated air to air heat exchanger: effectiveness of air to air heat exchanger, coefficient of performance and specific fan power of air handling unit. A daily performance of air handling unit is conducted. Effectiveness of supply side of air to air heat exchanger in range of 42.4 % to 52.5 % is received. Coefficient of performance in range of 1.50 to 2.08 and specific fan power of air handling unit in range of 1.39 kW/(m3/s) to 2.08 kW/(m3/s) are received. It was found experimentally that effectiveness of air to air heat exchanger depends on values of mass flow of supply and the exhaust air. High values of mass flow of the exhaust air responds to high effectiveness of supply side of air to air heat exchanger.
Reference8 articles.
1. Larson K., Pihlquist F.. Methods of Increasing Thermal Efficiency of a Counter Flow Air to Air Heat Exchanger. (Master of Science Thesis, Chalmers University of Technology, Goteborg, Sweden, 2011)
2. Pisarev V., Rabczak S., Nowak K.. J. Ecol Eng.,17(5),l63-172, (2016)
3. Heat Transfer and Effectiveness Analysis of a Cross-Flow Heat Exchanger for Potential Energy Recovery Applications in Hot-Humid Climate
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献