Abstract
A case study represented by an assisted living facility in Norway is modeled utilizing physics-based data-driven digital twin (DT) of the indoor thermal spaces with indoor temperature. Autoregressive Distributed Lag (ARDL), Machine Learning (ML), and Non-linear Autoregressive (NARX) models with timeseries and sliding-window cross-validation are compared. Results show that NARX models have the highest accuracy, with a MAPE score of 0.03%. In addition, the sliding-window enhanced the models’ accuracy and reduced the cyclical pattern for the autocorrelated values. The HVAC systems in this study case are representative of those found in Norwegian buildings, making the digital twin calibration applicable to other facilities.
Reference20 articles.
1. Deal E.G., The european green deal, Communication from the Commission to the European Parliament, the European Council, the Council, the European Economic and Social Committee and the Committee of the Regions. Brussels (2020).
2. Renewable energy production capacity and consumption in Europe
3. Have fossil fuels been substituted by renewables? An empirical assessment for 10 European countries
4. Demand-side management and European environmental and energy goals: An optimal complementary approach
5. Commission E., Energy performance of buildings directive (2023), accessed: 2023-12-11, https://energy.ec.europa.eu/ topics/energy-efficiency/energy-efficient-buildings/energy-performance-buildings-directive_en#documents