Abstract
The indoor airflow with a natural ventilation system was numerically calculated using the laminar and turbulent approach. In the chemical laboratory of the Technical University of Ambato, the computational code OpenFoam demonstrated an ability to numerically predict flow patterns. The design contemplated the natural ventilation system considering the laboratories’ working conditions not only in summer, but also in a winter week. These two operating conditions are calculated on a fully open and closed environment. For a room with a capacity of 20 people, the climate data average values were recorded at 14.0 ° C, 81.7%, 1.7 m /s for temperature, relative humidity, and wind speed, respectively. Furthermore, the demonstration has shown that the homogeneous occupancy air speed average is was 0.7 m / s with a facade air intake of 1.0 m / s 0.6 m / s in the room valid for the exchange of air and evacuation of pollutants. The maximum pressures were found in the lower part of the laboratory. This prevents the modification of the thermo-hygrometric conditions.