Author:
Zhang Xinwen,Kim Sang Yeop,Park Jong Ho,Choi Ji Su,Kim Chul,Rhee Kyu Nam,Jung Gun Joo
Abstract
This study explores the effects of heating demand and hot water temperature on energy efficiency in a domestic gas boiler (DGB). Mock-up experiments were conducted using two types of boilers with different capacities (i.e., 11.6 kW and 23.3 kW of non-condensing boilers, 16.3 kW of condensing boiler) for comparative analysis. As results, for space heating, the efficiencies of non-condensing boilers (i.e., 11.6 kW and 23.3 kW) and condensing boiler (i.e., 16.3 kW) decreased by 12-44%, 15-46%, and 2-22% respectively as the heating load ratios were changed from 100%-25%. When the supply hot water temperature settings decreased from 55℃ to 45℃, the efficiencies were reduced by 13.6% (11.6 kW) and 53.3% (23.3 kW). For the condensing boiler, an efficiency reduction rate was 16.7% as the hot water temperatures dropped from 45℃ to 35℃. Also, since the boiler capacity depends on domestic hot water (DHW) load, the daily heating demands of space heating and DHW load were analyzed. In the results, reducing the lower limit of heating output could be more effective in improving the boiler efficiency for space heating. To provide sufficient DHW demand, it is required to maintain the upper limit of the heating output.
Reference8 articles.
1. Zhou Z., Wang C., Sun X., Feng F. G, W., Zillante G., Heating energy saving potential from building envelope design and operation optimization in residential buildings: A case study in northern China, J Clean Prod. 174 (2018)
2. Cao X.,Dai X., Liu J., Building energy consumption status worldwide and the state-of-the-art technologies for zero-energy buildings during the past decade. Energy Build., 128 (2016)
3. Park C., Kim L.. A development of test method on the energy consumption efficiency of domestic gas boiler below 70 kW. J. Energy Eng., 23 (2016)
4. Rhee K.N., Jung G.J., Improvement methods of individual boiler heat source considering reduced heating load of Low-energy apartment buildings. J. KIAEBS, 14 (2020)
5. Yu B.H., Seo B.M., Moon J.W., Lee K.H., Analysis of the part load ratio characteristics and gas energy consumption of a hot water boiler in a residential building under Korean climatic condition. Korean J. Air Cond. Refrig. Eng., 27 (2015)