Impact of Layer Configuration and Chilled Water Temperature on the Cooling Capacity of Thermally Activated Light Shelf (TALS) System

Author:

Park Jong-Ho,Kim Sang-Yeop,Choi Ji-Su,Kim Chul,Rhee Kyu-Nam,Jung Gun-Joo

Abstract

Light shelves provide a function to control direct sunlight and introduce daylight into indoor spaces. Also, chilled water flowing in the light shelf can mitigate local cooling demands in perimeter zones. Therefore, in this study, a thermally activated light shelf (TALS) system was proposed, and the TALS’s radiative cooling capacity was evaluated. To do this, a mock-up chamber was developed using prototypes of TALS systems based on panel configurations. It is included: ‘Insulated’ (INS), ‘Air layer’ (ARL), and ‘Air layer with fans’ (ARF), which were designed to increase thermal insulation, natural convection, and forced convection in the TALS panels, respectively. The experiment showed that the ARL and ARF increased cooling capacity by 29% and 57% compared to the INS. Natural convective heat transfer and fan-forced airflow in the TALS's air cavity contributed to improving cooling capacity. With the INS and ARL, the air temperature was recorded at 28.6°C, which requires additional space cooling. The ARF reduced air temperature up to 2.0°C because the TALS cavity fans expedited convective heat transfer and mixing air between the cavity and test chamber. The results of this study could be used to estimate TALS cooling capacity and propose an optimal design in buildings.

Publisher

EDP Sciences

Subject

General Medicine

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3