Author:
Hruntovich N.V.,Kapanski A.A.,Baczynski D,Vagapov G.V.,Fedorov O.V.
Abstract
The development of the existing water supply system in towns and villages involves the use of frequency converters and specialized control algorithms that can maintain the pressure level established in the supply grid within certain limits. The implementation of the standard scheme includes the elimination of the water tower, which, on the one hand, reduces the cost of its maintenance. On the other hand, in emergency situations, the water tower can still supply water to the consumer, which increases the time of uninterrupted water supply during repairs. The article reveals a method of increasing the energy efficiency of transporting drinking water with the help of a water tower by eliminating the excessive pressure of the water rise when using frequency converters. Our research that involved more than 300 pumping stations, allowed to establish the average value of the excessive pressure of water rise, which reached 0.36 MPa. For the wells under study, optimization of the pump operation modes revealed the energy-saving potential of up to 52% due to excessive pressure reduction and up to 2.0% due to a decrease in starting power at the time of engine acceleration.
Reference15 articles.
1. Principles of energy saving in water supply and sewage systems
2. Dabadgaonkar S., Sen A.K., Controlling of Pump Onboard Ship using Variable Frequency Drive with Three-phase Inverter and Three Phase Induction Motor, MIT International Journal of Electrical and Instrumentation Engineering, 1(2) (2011)
3. Energy indicators and savings in water supply
Cited by
13 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献