Author:
Ren C.,Weng J.H.,Yan J.N.,Wang L.,She H.L.,Cui X.Y.
Abstract
Given its configuration and operation conditions, the performance of a counter-flow microchannel heat exchanger (MCHX) is evaluated through detailed calculations. The fluids, both liquid water and air, are considered as continuum flow flowing in microchannels. The MCHX has 59 sheets, and each sheet has 48 microchannels. The microchannels for both fluids have the same cross section of 0.8mm×1mm and same length of 200mm. Log mean temperature difference method is adopted for this evaluation. Using appropriate equations, the properties of air-water vapor mixture are calculated based on that of the two components. Given the inlet temperature for liquid water(35℃) and air (170℃),the calculated outlet temperature for both fluids are 55.5℃ and 43.3℃, respectively. The results also show that the air at the outlet is saturated. The overall heat transfer coefficient reaches 100W/m2ꞏK, which is much higher than that of conventional heat exchanger with similar fluid combinations.
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献