Analysis and treatment of current unbalance abnormal situation of 750 kV double-circuit parallel transmission line

Author:

Xie YadiORCID,Li Shan,Wang Chong,Yang Dingqian

Abstract

At present, the biggest problem faced by short-distance double-circuit parallel lines is the three-phase parameter asymmetry problem caused by non-transposition. This leads to three-phase current asymmetry, especially during heavy load performance is more prominent. Take a 750 kV double circuit parallel erection line in actual operation as an example, use EMTPE electromagnetic transient simulation software to simulate and analyze the current imbalance phenomenon. This paper studies the influence of phase sequence arrangement, distance between loops, distance between wires, line length, equivalent impedance, ground wire conditions and line power flow on current imbalance, and puts forward reasonable restraining measures. The simulation results show that when the line power flow is heavy, the double circuit lines are arranged in the same phase sequence and the distance between circuits is relatively short, there will be a large amplitude of zero sequence current on the line, mainly circulation current. If it is not suitable to adjust the protection measures, it can be considered to adjust the double-circuit lines to reverse phase sequence operation mode. The research results can provide reference for the engineering design of double-circuit parallel transmission lines.

Publisher

EDP Sciences

Subject

Safety, Risk, Reliability and Quality

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3