Author:
Zhu Jianjun,Lei Xinglie,Su Ziming,Liu Ting,Liu Kai,Yu Guangkai,Zhu Linyue
Abstract
This paper expounds the working principle of non-contact voltage detector and the electric field sensor which made by the technology of microelectromechanical systems (MEMS), determined the requirements of the detecting area and the threshold of the detector through simulation, and correct the threshold by carrying out experiments, which shows that by setting the threshold of the detector at 25kV/m, when the detector is 10-15m away from the conductors, or 2m away from the tower toward the conductor at the tower body whereas the same high as the conductor or on the crossarm, the detector can effectively identify whether the conductor is power on or off. The MEMS no-contact voltage detector and the method put forward by this paper can solve the problem of voltage detecting on UHV transmission lines, which has wide popularization and application value.
Reference22 articles.
1. Khan T H, Kabir S M L, Hussain S, et al. Design and implementation of a low cost electricity meter testing bench[C]// Industrial Electronics & Applications (ISIEA), 2010 IEEE Symposium on. IEEE, 2010:34-39.
2. Jiang T, Huang X, Yang Y, et al. Study on anti-interference of high voltage ultraviolet electroscope[C]// Automation Congress, 2008. Wac. IEEE, 2008:1-4.
3. He LI, Zhixiang DENG, Chuang WANG, et al. Study on Electrical Inspection’s Dead Zone of Capacitive Detector[J]. Electrical & Energy Management Technology, 2014(15):10-13.
4. DL/T 740-2014 capacitive type voltage detectors[M]. China Power Press, 2014.
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献