The use of non-metal materials in the filler units of cooling towers with circulating water supply system

Author:

Dmitriev Andrey V.,Madyshev Ilnur N.,Khafizova Aliya I.

Abstract

The design of cooling tower`s filler unit, consisting of inclined-corrugated contact elements, and made of polymer material, is developed and described in this research paper. The experimental studies were conducted to determine the efficiency of cooling the circulating water in the proposed cooling tower. The authors obtained the results of evaluating the heat-mass transfer efficiency coefficient of cooling tower, when changing the mass flow rates of liquid and gas phases. The research results showed that the highest efficiency of cooling the circulating water is observed at relatively low irrigation densities equal to 15-25 m3/(m2·h), while the heat-mass transfer efficiency of cooling tower achieves 72%.The use of non-metal materials as the main elements of cooling tower allows to abandon the use of chemical reagents against bacteria and microorganisms in favor of circulating water ozonation method.

Publisher

EDP Sciences

Subject

General Medicine

Reference29 articles.

1. Polymeric drop-film sprinklers for cooling towers

2. Ponomarenko V.S. etc., Cooling towers of industrial and energy enterprises: a reference manual (Energoatomizdat, Moscow, 1998).

3. Heat and Mass Exchange Packing for Desinfection of Circulation Water in Electric Field

4. Hydrodynamic operating regimes for a combined heat-and-mass exchanger

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3