Suryoputro M. Ragil,Buana Fajar Aga,Sari Amarria Dila,Rahmillah Fety Ilma
Abstract
According to the theory of fire triangle, the existence of combustible materials, heat, and oxygen can cause fire disaster. KH. Mas Mansur building, Islamic University of Indonesia has a fire protection, but rarely to be checked regularly and the number of equipment is less standard as well as the lack of an evacuation route map to facilitate the evacuation process. Inside the building also does not provide safety signs such as the evacuation directions, exit, and warning in case of fire. Therefore, researchers analysed the infrastructure of prevention and control in the building KH. Mas Mansur. Researchers used the method of observation, interviews, and checklist to know the condition directly, and compare with the standard regulations. Results concordance rate of existing infrastructure is 67% fire extinguisher, hydrant box 56%, 71% alarms, sprinkler 0%, 40% detectors, emergency doors 71%, 50% emergency stairs, assembly point 0% and directions 0%. The current results were below the standard of at least 80%. As for recommendations, researchers create a new evacuation map then put the existing infrastructure according to standard regulations, and it had consulted with the specialist of Occupational Safety and Health in the field of fire.