Author:
Fahruddin A'rasy,Muslimin Muslimin,Susilo Ginanjar Deni,Akbar Ali
Abstract
The cooling system is an essential part of the production process within the plant. In the cooling system using cooling tower, efficiency can be improved by increasing the effectiveness of cooling through nozzle modification. This study aims to determine the effect of diameter and number of nozzle holes on cooling effectiveness. The data were taken from the experiments using prototype of counterflow cooling tower with dimension of high x cross-sectional area are 120 cm x 40 cm x 40 cm. Diameter varied by 1; 1.5; and 2 mm, while the number of nozzle holes 4; 8; 16. The results show that the highest cooling effectiveness was achieved at nozzle diameter 1.5 mm with the number of holes 8 that is 38.77%.
Reference15 articles.
1. A study on multi-nozzle arrangement for spray cooling system in natural draft dry cooling tower
2. Vitkovic P., “Influence of a Nozzle Type on the Thermal Performance of the Fill,” in Proceedings of the 3rd World Congress on Mechanical, Chemical, and Material Engineering (MCM’17) (2017)
3. Zein A., A. et al. “Modification of Condenser Nozzle and Cooling Tower Exit Screen to Increase Condenser Performance,” Proceedings World Geothermal Congress 25-29 (2010)
4. Alkhedhair A., Guan Z., Gurgenci H., Jahn I., He S., “Experimental study on inlet air cooling by water spray for natural draft dry cooling towers enhancement,” Proc. 19th Australas. Fluid Mech. Conf. (2014)
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献