Affiliation:
1. Korea Electrotechnology Research Institute
Abstract
As a way to expand electric capacity in power line with hovering of electric power demand, STACIR/AW (super thermal-resistant Al alloy conductors Al-clad Invar-reinforced) overhead conductor which cans double ampacity has been developed. The STACIR/AW power line is mechanically composite stranded wire composed of INVAR/AW stranded wire as core for sag control and heat-resistant aluminum alloy for delivering doubled electric current. Recently, in order to ensure stable line operation and to predict its span of life, the changes of thermal properties for STACIR/AW have been investigated. In the present work, the changes of strain with temperature and the creep behavior as important factors in sag control will be presented. The transition temperature of STACIR/AW 410sqmm was estimated approximately 130°C and the creep rates were decreased with temperatures.
Publisher
Trans Tech Publications, Ltd.
Subject
Mechanical Engineering,Mechanics of Materials,Condensed Matter Physics,General Materials Science
Reference9 articles.
1. B. E. Shim, U. J. Woo and J. K. Choi: KEPCO Technical Report TR. 00PJ09 (2001).
2. S. Sakabe et. al.: IEEE. SM SM683-3 (1980).
3. A. Tanaka et. al.: Hitachi Cable Review, No. 1 (1982).
4. L. Pawlowski, D. Lombard and P. Fauchais: J. Vac. Sci. Tech. A3 (1985), p.2494.
5. C. E. Guillaume, C. R. Acad: Sci., Paris, Vol. 136 (1903).
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献