Disturbance Voltage Induced on the Intelligent Electronic Device Ports due to Switching Operations in Gas Insulated Substation

Author:

Ji Jian Fei1,Liu Xiao Fan2,Yuan Yu Bo3,Yang Yi Fei4,Jiao Chong Qing2

Affiliation:

1. Jiangsu Electric Power Co.

2. NCEPU

3. Jiangsu Electric Power Company Research Institute, China

4. Nanjing University of Science and Technology

Abstract

There is great concern on the electromagnetic compatibility problem of electronic equipments in an intelligent substation, due to the compact structure resulted from high degree of integration between the primary electrical equipments and secondary electronic equipments. The very fast transient electromagnetic disturbance (VFTED) resulted from the gas insulated substation (GIS) switching operation has potential impact on the electronic equipments by the electromagnetic coupling between the VFTED and the circuit of “sensor-cable-intelligent electronic device (IED)”. This paper presents both experimental and theoretical results of the disturbance voltage induced on the ports in control cabinets during the disconnectors operating in a 500kV GIS substation. The considered ports are connected to a current transformer (CT) equipped nearby GIS switcher via a KVVP cable. The results show that the peak value, the duration time and the frequency range of the transient waveform are about 400V, 2 μs, and below 40 MHz.

Publisher

Trans Tech Publications, Ltd.

Reference8 articles.

1. Yizhuang Huang, in: EMC technology for IED in substations, Power System Protection and Control, Vol. 36, No. 15 (2008), pp.6-9.

2. Rao M M, Thomas M J, and Singh B P, in: Electromagnetic Compatibility, IEEE Transactions on, Vol. 49, No. 2 (2007), pp.313-321.

3. Baoming Xiao, Xuemei Shen, Jinghao Jian, et al., in: Emi Analysis and Test of Intelligent Component on Smart Substation, Chengdu Sichuan China(2013).

4. CIGRE 124: Guide on EMC power plants and substations (1997).

5. CIGRE C4. 208: EMC within power plants and substations (2012).

Cited by 2 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

1. A Measurement System of Transient Overvoltage of Secondary Equipment Port During Digital Substation Switch Operation;2023 IEEE 3rd International Conference on Power, Electronics and Computer Applications (ICPECA);2023-01-29

2. Coupling Characteristics of Electromagnetic Disturbance of On-Site Electronic Device Power Port in Substations and Its Suppression;IEEE Transactions on Electromagnetic Compatibility;2021-10