Affiliation:
1. State Nuclear Electric Power Planning Design & Research Institute
2. Northeast Dianli University
Abstract
Boiler tube leakage is the major reason of affecting the safe operation of the unit now, there are 3 methods of the "four tube" leakage detection: Traditional method, filtering method and acoustic spectrum analysis, acoustic spectrum analysis is the common method, but this method have low sensitivity and the sensor damage easily. Therewith, designed the special acoustic catheter with acoustic resonance cavity type, proved by experiments, the acoustic catheter with acoustic resonance cavity type can enhance leakage sound, can accurately extract leakage signals, has high sensitivity, and can avoid the effect of sensor by fire and hot-gas when the furnace is in positive pressure situation, reduce the installation and maintenance costs of the boiler tube leakage monitor system.
Publisher
Trans Tech Publications, Ltd.
Reference10 articles.
1. A. Cinar, C. Undey, Statistical process and controller performance monitoring., Proceedings of the American Control Conference, 1999, p.2625–2639.
2. P. M. Frank, Fault diagnosis in dynamic systems using analytical and knowledge-based redundancy-a survey and some new results., Automatica, vol. 26, 1990, p.459–474.
3. P. M. Frank, X. Ding, Survey of robust residual generation and evaluation methods in observer-based fault detection systems., J. Process Control, vol. 7, 1997, p.403–424.
4. S. Yoon, J. F. MacGregor, Statistical and causal model-based approaches to fault detection and isolation., AIChE J, vol. 46, 2000, p.1813–1824.
5. S. Yoon, J. F. Mac Gregor, Fault diagnosis with multivariable statistical model. Part I: Using steady fault signature., J. Process Control, vol. 11, 2001, p.387–400.