Abstract
A 1000MW ultra-supercritical unit was studied to gain the energy consumption characteristics by means of thermodynamic analysis. Comparing with the designed conditions, the power generation efficiency under real operation is much less; especially under 50% and 100% rated loads. The higher superheated steam temperature and lower reheat temperature were found to explain that. At the real running, the higher superheated steam temperature induced more attemperation water, while reheat temperature lower than the designed point would decrease the power output. Aiming at solving issues about temperature control in unit operation, several details could be paid extra attention to. For instance, attemperating water comes from outlet of the high-pressure heaters would have a much slighter influence on generating efficiency.