Affiliation:
1. Guangzhou Special Pressure Equipments Inspection and Research Institute
2. Changsha University of Science and Technology
Abstract
The boiler make-up water pretreatment system and desalination system of 2×1000MW units in Taishan power plant were investigated and analyzed,and their corrosion risk were assessed . The results showed that the change of seasons had no effect on the dosage of coagulate in boiler make-up water pretreatment system and the system had advantages of economic operation, simple maintenance, however, corrosion risk might exist in equipment; for desalination system, carbon remover could be omitted and it had a large cycle water production, and the water quality of the mixed bed is good, however, the effect of iron removal and high efficiency filter backwashing is poor, In addition, corrosion existed in both acid and alkali regeneration system as well as in drainage system, steam turbine and effluent treatment equipment.
Publisher
Trans Tech Publications, Ltd.
Reference5 articles.
1. A. Banweg. Boiler and Feed water Treatment [J]. Shreir's Corosion, 2010, 4(28): 2971-2989.
2. Guoqiang Li, Lijuan Yang. Analysis of Power plant boiler make-up water treatment problem[J]. China New Technologies and Products, 2013, 03: 117.
3. Adham S, Hussain A, Minier Matar J, et al. Screening of advanced produced water treatment technologies: overview and testing results[J]. IDA Journal of Desalination and Water Reuse, 2013, 5(2): 75-82.
4. Cheng Li. Design and layout characteristics for boiler make-up water treatment system Nanning power plant . [J]. HongShui river, 2013, 32(1): 93-96.
5. Crispin Hales, Kelley J. Stevens, et al. Boiler feedwater pipe failure by flow-assisted chelant corrosion[J]. Engineering Failure Analysis, 2002, 9(2): 235-243.
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献