Abstract
The structural integrity of a BWR nuclear power plant can be compromised due to severe dynamic loads. Acoustic loads coming from a Safety Relief Valve branch can be adversely amplified if the steam flow is increased at the Main Steam Piping. This phenomenon has been reported previously in one BWR nuclear power plant. Its steam dryer was fractured and loose parts were generated due to high-cycle fatigue. This event has driven the United States Nuclear Regulatory Commission to issue specific regulations to evaluate acoustic loads which would be detrimental to the BWR steam dryer. In this paper, the acoustic loads were simulated when the steam flow is incremented from normal operation conditions to an Extended Power Uprate condition. It was analyzed, when the output power was incremented 14% and 28%. The initial conditions were determined with Computational Fluid Dynamics under steady state condition. This data was used in subsequent transient analysis. The model of Large Eddy Simulation was used and the acoustic simulation was performed with the Fowcs Williams and Hawkings Method. The Power Spectral Density was obtained with Fast Fourier Transform. The frequency peaks were found between 148 Hz and 155 Hz. These results are consistent with those obtained with the Helmholtz model and other results reported in the open literature. The results show that the peak pressure can be increased up to six times in resonance conditions, corresponding to a power uprate of 28%.
Publisher
Trans Tech Publications, Ltd.
Subject
Condensed Matter Physics,General Materials Science,Radiation
Reference16 articles.
1. S.A. Hambric, T.M. Mulcahy, V.N. Shah, T. Scarbrough and C. Wu, Flow-Induced Vibration Effects on Nuclear Power Plant Components due to Main Steam Line Valve Singing, Proceedings of the Ninth NRC/ASME Symposium on Valves, Pumps and In-service Testing, vol. 6, pp. 3B: 49- 3B: 69, (2006). 2. G. DeBoo, K. Ramsden, R. Gesior, B. Strub, Identification of Quad Cities Main Steam Line Acoustic Source and Vibration Reduction, Proceedings of the Pressure Vessels and Piping Conference, vol. 4, pp.485-491, (2007). 3. R. Morita, S. Takahashi, K. Okuyama, F. Inada, Y. Ogawa and K. Yoshikawa, Evaluation of Acoustic and Flow Induced Vibration of the BWR Main Steam Lines and Dryer, Journal of Nuclear Science and Technology, 48: 5, pp.759-776, (2012). 4. K. Okuyama, A. Tamura, S. Takahashi, M. Ohtsuka and M. Tsubaki, Flow-Induced Acoustic Resonance at the Mouth of One or Two Side Branches, The 8th International Topical Meeting on Nuclear Thermal-Hydraulics, Operation and Safety, vol. 249, pp.154-158, (2012). 5. S. Ziada, P. Lafon, Flow-Exited Acoustic Resonance Excitation Mechanism, Design Guidelines, and Counters Measures, Applied Mechanics Reviews, vol. 66, pp.1-22, (2014).
|
|