Performance Comparison of Typical Built-In UHF Sensors Used for GIS PD Detection

Author:

Jia Yong Yong1,Yang Jing Gang1,Rong Lin2,Tao Feng Bo2

Affiliation:

1. State Grid Jiangsu Electric Power Company Research Institute

2. NARI Technology Co., Ltd

Abstract

The UHF method is one of the most important partial discharge (PD) detection means for GIS, while sensor technique is the key factor of the UHF method. In comparison with external sensors, built-in sensors can achieve higher sensitivity. In this paper, two parameters were quoted to evaluate the performance of the sensor, which are He and S11. He refers to the PD detection sensitivity of sensor; S11 refers to the impedance matching property of the sensor. The paper firstly designed a simulation model of sensor performance evaluation, and then studied the performance differences of four typically used or researched built-in UHF sensors (i.e., disc-type, dipole-type, spiral-type and logarithmic-type) by simulation tools of CST. The conclusions of the paper can provide a reference for performance evaluation and type selection of UHF built-in sensor. Keywords: Gas Insulated Switchgear (GIS), Partial Discharge (PD), UHF, Sensor, Sensitivity

Publisher

Trans Tech Publications, Ltd.

Reference11 articles.

1. HAMPTON B F, MEATS R J. Diagnostic measurements at UHF in gas insulated substations [J], IEE Proceedings-Generation, Transmission and Distribution, IEE Proceedings C, 1988, 135(2): 137-145.

2. PEARSON J S, HAMPTON B F, SELLARS A G. A continuous UHF monitor for gas-insulated substations [J], Dielectrics and Electrical Insulation, IEEE Transactions on, 1991, 26(3): 469-478.

3. TANG Ju, LIAO Hua, ZHANG Xiao-xing, et al. GIS partial discharge UHF on-line monitoring system based on virtual instruments [J]. Journal of Chongqing University (Natural Science Edition), 2008, 31(1): 29-33.

4. LI Zhong, CHEN Hua-jie, HU Di-jun, et al. Research on partial discharge in GIS based on UHF method detection[J]. Automation of Electric Power Systems, 2004, 28(1): 41-44.

5. CUI Zai-yuan, JIANG Chang-yuan, DU Ji-jun, et al. On-line UHF partial discharge monitoring system for prevention of failures in gas-insulated switchgears[J].  Power System Technology, 2007, 31(7): 51-54.

Cited by 2 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

1. A Novel Composite Sensor for UHF Partial Discharge and Gas State Measurement in GIS;IEEE Transactions on Instrumentation and Measurement;2024

2. Analysis of a Partial Discharge Defects in GIS Support Insulator;2021 IEEE 2nd China International Youth Conference on Electrical Engineering (CIYCEE);2021-12-15