Abstract
The stability of the high voltage arm resistors has a strong influence on the performance of the resistance high DC voltage divider. So by analyzing the main parameters that affect the resistor value change, including voltage coefficient, power coefficient and so on, a new matching method is proposed to make a high precision high DC voltage divider in this paper. Based on the principle of pairing the resistors and adjusting the big and small ones, a high precision high DC voltage divider could be made with the voltage variation less than 0.005%, even on the condition of using high voltage coefficient and power coefficient resistors.
Publisher
Trans Tech Publications, Ltd.
Reference8 articles.
1. Leren Wang, Suhan Zhang. Voltage summation method for determining the voltage dependence ration variation of precise high DC voltage dividers. Acta Metrologica Sinica. Forum 24 (2003) 46-48.
2. Hongqing Xiao, Weicheng Chen, Ming Lei, Yun Lu, Jun Chen, 200 kV self correction standard DC voltage divider design and research (The electrical test technology academic exchange conference proceedings, 2002).
3. E. Houtzager et al. Selection and characterization of resistors for a HVDC reference divider. CPEM 2012 Conf. Dig. (2012)197-198.
4. Xiaodong Wang. New thick film resistor in high voltage system, J. Electronic Components $ Materials . 5 (1987) 8-43.