Abstract
The power loss in laminated transformer cores is always greater than the nominal loss of the electrical steel laminations, by a factor known as the building factor. This paper discussed result of an investigation towards the effect of using two different Grain-Oriented Silicon Iron (3%SiFe) materials to the 100kVA three phase distribution transformer. The thicknesses of the material that have been used in this research are 0.23mm and 0.27mm. The transformer core will be assembled with 60o T-joint with 5mm mitred corner overlap length. Power loss has been measured using no-load test with 29 layer of lamination while nominal loss measured using Epstein test frame. At the operation mode flux density, 1.5T, the building factor of the transformer model core material with 0.23mm thickness is 1.219 while with the building factor for 0.27mm thickness is 1.250. This shows that thinner transformer core lamination is better than the other one by 2.5% during operation mode.
Publisher
Trans Tech Publications, Ltd.
Reference5 articles.
1. Boon, C.R., Thompson, J.E., & Inst. P A. (1965). Alternating and rotational power loss at 50c/s in 3% silicon-iron sheets. Proceeding The Institution of Electrical Engineers , 112, 2147-2151.
2. teNyenhuis, E., Mechler, G.F., & Girgis, R.S. (2001). Other factors contributing to the core loss performance of power and distribution transformers. IEEE Transaction on Power Delivery, 16, 648-653.
3. Daut, I. (1991). Investigation of flux and loss distribution in transformer cores assembled from amorphous powercore materials. Dissertation. University of Wales, Cardiff.
4. Pfutzner, H., & Schonhuber, P. (1991). Flux distributions analysis in a mitred transformer core corner. Journal of Magnetism and Magnetic Materials. 101, 86-66.
5. Moses, A. J, & Thomas, B. (1974). Problems in the design of power transformers. IEEE Transaction on Magnetics, 10, 148-150.