Influence of throttling and nozzles switching sequence on indicator of water distribution uniformity in cooling tower model

Author:

Orel Vadym, ,Matsiyevska Oksana,Pitsyshyn Bohdan,Tseniukh Maksym

Abstract

The article analyzes factors leading to non-uniformity of water distribution in cooling towers. These include imperfections in the design of pipelines and nozzles of the water distribution system of cooling towers. Previous studies conducted on a model of the water distribution system of the tower-type cooling system at Rivne Nuclear Power Plant have revealed uneven water distribution on the nozzles. Simulation of the simultaneity of nozzle activation showed that the nozzle that is activated first has the highest flow rate. Therefore, to achieve acceptable uniformity of water distribution, this nozzle was throttled using a throttling orifice plate. It has been shown that such throttling is effective even in the presence of hydrodynamic cavitation at orifice plate diameter ratios of 0.449...0.624. When four model nozzles are activated one after the other, the flow rate of the first nozzle decreases both with and without throttling. At the same time, increase in the number of working nozzles up to four does not significantly affect the flow rate of the first nozzle.

Publisher

Lviv Polytechnic National University

Subject

General Medicine

Reference20 articles.

1. 1. Fedyaev, V. L., Mazo, A. B., Morenko, I. V., Gainullin, R. F. and Gainullina R. F. (2009). On the efficiency of industrial cooling towers. News of higher educational institutions. Problems of Energy, 1-2, pp. 15-24. (in Russian)

2. 2. Lyakhovetskaya-Tokareva M.M. (2015). The ways of rational use of cooling towers. Bulletin of the Prydniprovsk State Academy of Civil Engineering and Architecture, 3 (204), pp. 36-43. (in Russian)

3. 3. Ponomarenko, V. S., Aref'ev, Ju. I. (1998). Industrial and Power Cooling Towers : Reference Guide. Jenergoatomizdat, Moskva. (in Russian)

4. 4. Zenovich-Leshkevich-Olpinskiy Yu., A., Shiroglazova, N. V. and Zenovich-Leshkevich-Olpinskaya, A. Yu. (2016). Improvement of Systems of Technical Water Supply with Cooling Towers for Steam Power Plants Technical and Economic Indicators Perfection. Part 1. Enеrgеtika. Proс. СIS Higher Educ. Inst. аnd Power Eng. Assoc. 59 (3), pp. 235-248. (in Russian) https://doi.org/10.21122/1029-7448-2016-59-3-235-248

5. 5. Biletska, A. S., Shklyar, V. I., Dubrovska, V. V. and Borysyuk, V. D. (2011). Water Cooling Device of Cooling Tower of Cherkassky Thermal Power Station Efficiency Increase. Energy Technologies & Resource Saving. No. 3, pp. 70-73. (in Russian)

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3