Abstract
The method of fuel quality control is considered, which is based on the using of the oxygen sensor (without sensors of incomplete fuel combustion products). An algorithm for the electric drive of a fan is proposed, which is based on a step changing in the rotation speed. The choice of broadband oxygen sensor as a basis for the development of a fuel combustion control system is determined. In the course of experimental studies, the possibility of reconstructing the boiler by replacing a burner with an installed control system was demonstrated. The commissioning works were carried out with the installed system, the optimum operating conditions of the boiler were determined (with the formation of CO in the flue gases at a minimum level <50 ppm). The technical characteristics of the boiler operation under different loads (from 10 % to 100 %) are considered. Ecological and economic analysis of the developed fuel combustion control system was carried out.
Publisher
Periodica Polytechnica Budapest University of Technology and Economics
Cited by
30 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献