Abstract
This research presents an energy performance analysis of the heat pump system with internal heat exchanger (IHX). The mathematical model of the heat pump outlined in this paper has been created by the author, it is steady-state with lumped parameters. The experimental validation of the model has been carried out using R1234yf and R134a as refrigerant. The aim of this work is to compare the energy performance in a wide range of operating conditions of a monitored heat pump system using both refrigerants. Finally, the heating capacity for R1234yf was lower from 0.63 % to 7.54 % compared with R134a, while the compressor power was similar from 0.12 % to 3.51 %. The COP values of R1234yf were lower than those obtained of R134a, ranging from 1.39 % to 4.22 %.
Publisher
Periodica Polytechnica Budapest University of Technology and Economics
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献