Deformations in Power Transformers by Sweep Frequency Response Analysis and a Sample Field Study

Author:

GEZEGİN Cenk1ORCID,USTA Orhan CengizORCID

Affiliation:

1. ONDOKUZ MAYIS ÜNİVERSİTESİ

Abstract

Power transformers are expensive pieces of electrical equipment that are used to connect transmission and distribution networks. Power transformers are inspected and tested on a regular basis throughout production, shipment, installation, and operation. There are several ways for determining the mechanical integrity of power transformers. Power transformers are monitored using these diagnostic procedures, and any breakdowns and issues are avoided. Scanning Frequency Response Analysis (SFRA) is an efficient method for determining the condition of the transformer core and windings. To evaluate the state of the transformer winding, SFRA, winding direct current resistance, and winding capacitance tests were done in this study. In the case study, a comprehensive case analysis was done on the SFRA test findings for a 50/62.5 MVA power transformer, and the results were analyzed. The results reveal that the SFRA test finds structural winding problems in transformers with high accuracy.

Publisher

INESEG Yayincilik

Subject

General Earth and Planetary Sciences

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3