Author:
Rice Nancy,Streifel Andrew,Vesley Donald
Abstract
AbstractObjective:To quantitate the magnitude and consistency of positive (airflow out) and negative (airflow in) hospital special-ventilation-room (SVR) airflow.Design:A room-pressure evaluation was conducted during two seasons on a total of 18 rooms: standard rooms, airborne infection isolation rooms, and protective environment rooms. The pressures were measured using a digital pressure gaugepiezoresistive pressure sensor that measured pressure differentials. With doors closed, the rooms were measured a minimum of 30 times each for a cooling season and a heating season.Results:The standard rooms showed the least amount of variability in pressure differential, with an average of −0.2 Pa (median, −0.2 Pa), and an interquartile range (IQR) of 0.4 Pa. Airborne infection isolation rooms showed more variability in pressure, with an average of −0.3 Pa (median, −0.2 Pa) and an IQR of 0.5 Pa. Protective environment rooms had the greatest fluctuation in pressure, with an average of 8.3 Pa (median, 7.7 Pa) and an IQR of 8.8 Pa. Dramatic pressure changes were observed during this evaluation, which may have been influenced by room architectural differences (sealed vs unsealed); heating, ventilation, and air-conditioning zone interactions; and stack effect.Conclusion:The pressure variations noted in this study, which potentially affect containment or exclusion of contaminants, support the need for standardization of pressure requirements for SVRs. To maintain consistent pressure levels, creating an airtight seal and continuous pressure monitoring may be necessary.
Publisher
Cambridge University Press (CUP)
Subject
Infectious Diseases,Microbiology (medical),Epidemiology
Reference11 articles.
1. Guidelines for preventing the transmission of Mycobacterium tuberculosis in health-care facilities, 1994—CDC. Notice of final revisions to the “Guidelines for Preventing the Transmission of Mycobacterium tuberculosis in health-care facilities, 1994.”;Fed Regist,1994
2. Laboratory Space Pressurization Control Systems;Hitchings;ASHRAE Journal,1994
3. Ventilation for protection of immune compromised patients;Murray;ASHRAE Transactions,1988
Cited by
38 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献