Point-of-Use Membrane Filtration and Hyperchlorination to Prevent Patient Exposure to Rapidly Growing Mycobacteria in the Potable Water Supply of a Skilled Nursing Facility

Author:

Williams Margaret M.,Chen Tai-Ho,Keane Tim,Toney Nadege,Toney Sean,Armbruster Catherine R.,Butler W. Ray,Arduino Matthew J.

Abstract

Background.Healthcare-associated outbreaks and pseudo-outbreaks of rapidly growing mycobacteria (RGM) are frequently associated with contaminated tap water. A pseudo-outbreak ofMycobacterium chelonae–M. abscessusin patients undergoing bronchoscopy was identified by 2 acute care hospitals. RGM was identified in bronchoscopy specimens of 28 patients, 25 of whom resided in the same skilled nursing facility (SNF). An investigation ruled out bronchoscopy procedures, specimen collection, and scope reprocessing at the hospitals as sources of transmission.Objective.To identify the reservoir for RGM within the SNF and evaluate 2 water system treatments, hyperchlorination and point-of-use (POU) membrane filters, to reduce RGM.Design.A comparative in situ study of 2 water system treatments to prevent RGM transmission.Setting.An SNF specializing in care of patients requiring ventilator support.Methods.RGM and heterotrophic plate count (HPC) bacteria were examined in facility water before and after hyperchlorination and in a subsequent 24-week assessment of filtered water by colony enumeration on Middlebrook and R2A media.Results.Mycobacterium chelonaewas consistently isolated from the SNF water supply. Hyperchlorination reduced RGM by 1.5 log10initially, but the population returned to original levels within 90 days. Concentration of HPC bacteria also decreased temporarily. RGM were reduced below detection level in filtered water, a 3-log10reduction. HPC bacteria were not recovered from newly installed filters, although low quantities were found in water from 2-week-old filters.Conclusion.POU membrane filters may be a feasible prevention measure for healthcare facilities to limit exposure of sensitive individuals to RGM in potable water systems.

Publisher

Cambridge University Press (CUP)

Subject

Infectious Diseases,Microbiology (medical),Epidemiology

Cited by 32 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3