Assessment of Biogrowth at Two Different Environments of Nuclear Power Plant Cooling Water System Located at Southern Coast of India

Author:

Ganesh S.1ORCID,Retna A. Malar1,Wesley S. Godwin2,Murthy P. Sriyutha3,Rao T. Subba3

Affiliation:

1. Department of Chemistry, Scott Christian College (Affiliated to Manonmaniam Sundaranar University,Tirunelveli), Nagercoil-629003, India

2. Department of Zoology, Scott Christian College, Nagercoil-629003, India

3. 3Water & Steam Chemistry Division, Bhabha Atomic Research Centre Facilities, Kalpakkam-603102, India 4Homi Bhabha National Institute, Anushaktinagar, Mumbai-400094, India

Abstract

A systematic assessment of biogrowth development on titanium coupons exposed to ambient seawater (intake) and chlorinated seawater (pump house) environments of a coastal nuclear power plant was carried out. Titanium coupons were exposed for a period of 2 years and periodically removed at monthly intervals for biogrowth assessment. Biofouling biomass at the seawater intake station ranged from 0.8-12.5 kg m-2 during the 2 years of study. Continuous chlorination of 0.2 ± 0.1 mg L-1 and shock dose chlorination for 1 h/day at residuals of 0.4 ± 0.1 mg L-1 was very effective in reducing the biofouling load in the cooling water system. A reduction in fouling biomass of 95% was observed on titanium coupons between the intake and the pump house stations. Biofoulants recruitment was found to occur throughout the year at varying intensities. Diversity of organisms on the coupon was influenced by seasonality and distinct successional patterns were observed at the seawater intake. Barnacles were the dominant fouling organisms followed by mat forming ascidians, bryozoans, oysters, hydroids and seaweeds at the intake station. Sluggish biofouling development was observed on coupons at the intake due to the sub-tidal intake system (-5 m), which had a lesser load of meroplanktonic organisms. The study also showed that low dose continuous chlorination was an effective strategy for biofouling control in the cooling water system of the tropical power station which uses titanium heat exchangers for steam condensation.

Publisher

Asian Journal of Chemistry

Subject

General Chemistry

Reference62 articles.

1. Marine Biofouling on Moored Buoys and Sensors in the Northern Indian Ocean

2. T.S. Rao, Eds.: S. Rajagopal, H.A. Jenner and V.P. Venugopalan, Microbial Fouling and Corrosion: Fundamentals and Mechanisms, In: Operational and Environmental Consequences of Large Industrial Cooling Water Systems, Springer Inc., The Netherlands, pp. 95-126 (2012).

3. J.H. Rains, W.J. Foley and A. Hennik, Flow blockage of Cooling water to Safety System Components by Corbicula sp. (Asiatic clam) and Mytilus sp. (mussel), USNRC. Washington: D.C. Report No.: NUREG/CR 3054 (1984).

4. C.H. Henager, P.M. Daling and K.I. Johnson, Bivalve Fouling of Nuclear Power Plant Service-Water Systems: Factors that may Intensify the Safety Consequences of Biofouling, NUREG/CR–4070, Pacific Northwest Labs: Richland, WA, USA, vol. 3, p. 58 (1985).

5. C. Malmstrom, Nat. Educ. Knowledge, 3, 88 (2010).