Peducing the frequency of switching overvoltage in generator networks

Author:

Belsky R. A.1ORCID,Frolov V. Y.1ORCID,Zhiligotov R. I.1ORCID,Safonov E. P.1ORCID

Affiliation:

1. Peter the Great St. Petersburg Polytechnic University

Abstract

THE PURPOSE of the study is to study the problem of switching overvoltages in 10 kV generator networks. Using the Matlab Simulink package, create a model of common auxiliaries of a 10/0.4 kV power station, calculate the overvoltage at different sections of the current, evaluate the effect of vacuum switches on each other, evaluate the effectiveness of nonlinear overstrain limiters, with parallel switching.THE SCIENTIFIC SIGNIFICANCE consists in obtaining a method for calculating transients with simultaneous switching of several switches. THE PRACTICAL SIGNIFICANCE lies in the possibility of using the resulting model for a more accurate selection of protective equipment.METHODS. To create a model of common auxiliaries of 10/0.4 kV and the calculations of transition processes, it used a Matlab Simulink package. RESULTS. The article discusses switching overvoltages in their own needs of 10/0.4 kV. The influence of parallel switching of vacuum circuit breakers on the increase in the multiplicity of overvoltages is estimated. The influence of the specific energy intensity of nonlinear surge limiters on the multiplicity of overvoltages was also evaluated.CONCLUSION. This model showed that the parallel switching of two vacuum circuit breakers can increase the frequency of overvoltage by 20-40 %, which can lead to an increase in wear of both insulation of the protected equipment and the probability of re-breakdown in a vacuum chamber. Moreover, the higher the current cut, the higher the increase in the frequency of the overstrain, the multiplicity will also increase if the shutdown time between the switches is reduced. The main means of protection against switching overvoltages is a non -linear overstrain limiter, but when they are selected, the nominal working voltage is primarily taken into account, which leads to the fact that the increase in the frequency of overstrain from parallel switching can level the effectiveness of a nonlinear limiter.

Publisher

Kazan State Power Engineering University

Reference15 articles.

1. Evdokunin GA, Tiler G. Modern vacuum switching equipment for medium voltage networks (technical advantages and operational characteristics). 2nd ed. SPb: Publishing house Tertsiya; 2006. (In Russ).

2. Safonov E.P, Frolov V.Ya. Features of fault transient's in generator network of powerful electric power stations // Proceedings of the higher educational institutions. ENERGY SECTOR PROBLEMS. 2021. 23(1):105-118. (In Russ). DOI:10.30724/1998-9903-2021-23-1-105-118

3. Chervonchenko S.S, Frolov V.Ya. Research of the operation of an autonomous electrical complex with a combined composition of backup power sources // Proceedings of the higher educational institutions. ENERGY SECTOR PROBLEMS. 2022. 24(4):90-104. (In Russ). DOI:10.30724/1998-9903-2022-24-4-90-10

4. Pertsev A.A, Belkin G.S. Switching processes in vacuum circuit breakers with parallel connection of arc extinguishing chambers // Elektrotekhnika. 2022. (4):39. (In Russ).

5. Khalilov F.Kh. Protection of 6-35 kV networks from overvoltage. SPb: Energoatomizdat. 2002. (In Russ).

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3