This paper examines the thermal characteristics of a two-stage absorption refrigeration machine. When carrying out a numerical analysis, it turned out that the secondary generator’s temperature was not constant, and it was also found that the coefficient of thermal performance of this cycle increased significantly at the beginning, then stabilized at a certain value for the temperature degree of the primary generator. But this result is not the right value for calculating the absorption refrigeration cycle; it might cause crystallization inside the cycle and This was verified based on the thermodynamic relationship chart (h-X-T) for LiBr-water solution. In addition, the decisive point for determining the appropriate temperature is to study the change in refrigeration capacity in the process when the temperature of the generator changes. In this case, the design temperature for the primary generator should be in the range between the temperature corresponding to the highest refrigeration capacity and the temperature far from the crystallization phenomenon.
Publisher
Samara State Technical University
Reference10 articles.
1. Zakhidov R.A., Davlonov H.A. Prospects of solar cooling systems for buildings based on absorption refrigeration machines. Al’ternativnaja jenergetika [Alternative Power Engineering], 2022, vol. 5, no. 2, pp. 7–10. (in Russian)
2. USE OF SOLAR ENERGY HEAT IN ANIMAL BREEDING BUILDINGS
3. Mereutsa E.V., Sukhikh A.A. Analysis of energy efficiency of the air conditioning system based on an absorption refrigeration machine with connection of a heat pump plant and solar collectors. Problemy regional’noj jenergetiki [Regional Energy Challenges], 2023, no. 1 (57), pp. 99–110. (in Russian)
4. Suhail Ahmad Khan. “Comparative analysis of single and double effect LiBr-water absorption system”. 4th International Conference on Recent Innovations in Sciences Engineering and Management. March 2016.