Experience of using the NALCO 1392 scale inhibitor in the circulating water supply system of the Novovoronezh NPP

Author:

Dronov Dmitry M.,Gontovoy Aleksandr V.,Sarkisyan Yelena N.,Karandeeva Natalya V.

Abstract

Power facilities use large amounts of water to cool steam in the steam turbine condensers, and lubricating oils, gas and air in turbine sets. The key requirement for the quality of cooling water is to ensure normal vacuum in condensers. Cooling water must not form mineral and biological deposits and corrosion products in the system. Deposits of mineral salts in the condenser tube system, as well as in auxiliary cooling systems, lead to deterioration in heat exchange and a major decrease in the cost effectiveness of the power equipment operation, and require the heat-exchange equipment to be periodically cleaned. The source water used for cooling is normally taken from nearby water bodies (large rivers or lakes). Circulating water supply systems are used most commonly: these systems use repeatedly the same water inventory for cooling, and require only small amounts of water added to make up for evaporation losses. Coolers, in this case, are cooling towers, spray pools and evaporation ponds. The water chemistry should ensure the operation of equipment without any damage to its components or the loss of efficiency caused by the corrosion of the internal surfaces as well as without scale and sludge formation. It is exactly when using circulating water supply that a stabilizing treatment program is the most practicable way to ensure a cost-effective and environmentally friendly mode of operation. To inhibit scaling processes on the heat-exchange surfaces of the turbine condenser tubes at the Novovoronezh NPP’s unit 5, the cooling water was treated with the NALCO 1392 inhibitor. The results of the NALCO 1392 inhibitor pilot tests in the circulating water supply system (with a cooling pool) are presented.

Publisher

Pensoft Publishers

Subject

General Medicine

Reference11 articles.

1. Investigation of salt inhibitors for water chemistry of the main cooling water system with evaporative cooling towers.;Galanin;Yadernaya i radiatsionnaya bezopasnost S,2019

2. Analysis of methods to prevent and remove calcium carbonate deposition on heating surfaces.;Golovatenko;Proc. of the International Scientific and Practical Conference “Innovations in Construction – 2018”, 22–24 November. Bryansk. Bryansk State Engineering and Technological University Publ.,2018

3. Optimization of the operating modes of steam turbine condensers with regard for the cooling water cost. Izvestiya vuzov. Severo-Kavkazsky region.;Ilyenko;Tekhnicheskiye nauki,2006

4. Stabilization treatment of circulating and heating water.;Ivanova;Proc. of the 3rd All-Russian Conference “Chemistry and Chemical Technology: Achievements and Prospects”. 16–17 November. Kemerovo. Kuzbass State Technical University named after T.F. Gorbachev Publ.,2016