Abstract
In this paper, the risk of damages to humans and properties due to fire explosions in gasoline storage tanks is identified, and the effects of radiant heat on adjacent tanks are evaluated to present the necessary area to secure safety. A simulation was conducted to evaluate the effect of radiant heat (Maximum emission) on adjacent tanks in an oil storage tank fire due to environmental conditions (Wind speed and temperature) in the Northern Gyeonggi Province. The result indicated that the radiant heat released in the fire of an oil storage tank was increased by approximately 1.9 times by the maximum wind speed and the difference occurred in the range of 700~800 kW by the maximum temperature. If a storage tank fire occurs, securing approximately 34.4 m of holding area is necessary. In the future, evaluating the radiant heat emitted by the fire of gasoline storage tanks will be required by applying various environmental conditions, and through this, research on specific and quantitative holding area is required.
Publisher
Korea Institute of Fire Science and Engineering
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献